Pressure
Fundamentals of Pressure Sensor Technology
To begin our investigation of pressure sensors, we first must consider the physics on which the technology is based.
Basic Physics of Pressure Sensing
Static Pressure.
Pressure, P, is defined as force, F, per unit area, A:
Static Pressure.
Pressure, P, is defined as force, F, per unit area, A:
P = F/A | (1) |
The measurement of pressure is generally associated with fluids, either liquids or gases. A container filled with a liquid (see Figure 1) has a pressure (due to the weight of the liquid) at a point in the liquid of:
P = F / A = hw | (2) |
where:
h | = distance from the surface to the point |
w | = weight of the liquid (most liquids are nearly incompressible) |
Figure 1. The pressure at any given point in a confined liquid is determined by the weight of the liquid and the distance from the point to the surface.
|
w = mg/V | (3) |
where:
m | = mass |
g | = gravitational acceleration |
Note that this relation can be used to determine the height of the column
of liquid in a tank by measuring the pressure.
The density, , is given by:
= m/V | (4) |
Thus, the density of a liquid determines the pressure, P, exerted for a given height. Mercury is 13.6 3 denser than water, so would exert a pressure 13.6 3 that of water for a column of the same height. It should be noted that the pressure due to the height of a column of liquid is in addition to the atmospheric pressure acting on the surface of the liquid.
The height of a column of liquid is:
h = P/g | (5) |
Archimedes's principle states that "A body wholly or partially submerged in a liquid is buoyed up by a force equal to the weight of the liquid displaced."
Given a block of material submerged in a container of liquid (see Figure 2) with area A and length L, the downward pressure exerted on the top face is:
PD = hg | (6) |
Figure 2. Archimedes' principle states that an object submerged in a confined liquid will be buoyed up by the weight of the liquid it displaces. |
PU = (h + L) g | (7) |
giving a resultant pressure of:
PU - PD = Lg | (8) |
and the force is equal to the volume of the block multiplied by the weight
of the liquid displaced.
Figure 3. The pressure transmitted to a confined liquid is normal to
the liquid's surface, as can be observed by breaching one of the walls of
the container.
|
This is important in the construction of dams, given that they must resist the force of water. This pressure is called the static pressure.
forces to be generated easily by trading large movement of a small piston for small movement of a large piston (see Figure 4).
Figure 4. Pascal's law states that an increase in pressure at any point
in a liquid causes a corresponding increase at every other point in the
liquid.
|
This is due to the kinetic energy of the fluid:
PI = VO²/2 | (9) |
where:
= fluid density | |
VO | = fluid velocity |
Bernoulli's theorem states that for horizontal flow the following relation
holds:
PS = PO + PI | (10) |
where:
PS | = stagnation (or total) pressure |
PO | = static pressure |
This relationship is useful for determining the flow velocity in a variety
of applications. Rearranging the equation gives:
(11) |
Figure 5. A Pitot tube assembly can be used to measure the velocity of a moving fluid. |
Gases. Gases differ from liquids in two respects: they are very compressible, and they completely fill any closed vessel in which they are
Figure 6. The compressibility of gases is illustrated by nonlinear atmosphere
pressure as a function of altitude. |
Static pressure is measured under steady-state or equilibrium conditions, but most real-life applications deal with dynamic or changing pressure. For example, the measurement of blood pressure usually gives the two steady-state values of systolic and diastolic pressure. There is much additional information in the shape of the blood pressure signal, however, which is the reason for the monitors used in critical-care situations.
To measure changing pressures, the frequency response of the sensor must be considered. As a rough approximation, the sensor frequency response should be 5-10 × the highest frequency component in the pressure signal. The frequency response is defined as the highest frequency that the sensor will measure without distortion or attenuation.
Sometimes the response time is given instead.
Sometimes the response time is given instead.
For a first-order system, they are related as follows:
FB = 1/2 | (12) |
where:
FB | = frequency where the response is reduced by 50% |
= time constant where the output rises to 63% of its final value following a step input change |
Another issue is the remote measurement of pressure where a liquid coupling medium is used. Care must be taken to purge all air because its compressibility will corrupt the waveform.
Types of Pressure Measurements
Absolute pressure is measured relative to a perfect vacuum. An example is atmospheric pressure. A common unit of measure is pounds per square inch absolute (psia).
Differential pressure is the difference in pressure between two points of measurement. This is commonly measured in units of pounds per square inch differential (psid).
Gauge pressure is measured relative to ambient pressure. Blood pressure is one example. Common measurement units are pressure per square inch gauge (psig). Intake manifold vacuum in an automobile engine is an example of a vacuum gauge measurement (vacuum is negative gauge pressure).
Figure 7. The same sensor can be used for all three types of pressure
measurement; only the references differ.
|
The three types of measurements are shown in Figure 7. Note that the same sensor may be used for all three types; only the reference is different.
Differential pressures may be measured anywhere in the range—above, below, and around atmospheric pressure.
As previously noted, pressure is force per unit area and historically a great variety of units have been used, depending on their suitability for the application. For example, blood pressure is usually measured in mmHg because mercury manometers were used originally. Atmospheric pressure is usually expressed in in.Hg for the same reason. Other units used for atmospheric pressure are bar and atm.
The following conversion factors should help in dealing with the various units:
1 psi | = 51.714 mmHg |
= 2.0359 in.Hg | |
= 27.680 in.H2O | |
= 6.8946 kPa | |
1 bar | = 14.504 psi |
1 atm. | = 14.696 psi |
Example: Convert 200 mmHg to psi:
200 mmHg • 1 psi/51.714 mmHg = 3.867 psi
Figure 8. The typical pressure sensor has three functional blocks.
|
Pressure is sensed by mechanical elements such as plates, shells, and tubes that are designed and constructed to deflect when pressure is applied.
This is the basic mechanism converting pressure to physical movement. Next,this movement must be transduced to obtain an electrical or other output.
Figure 9. The basic pressure sensing element can be configured as a C-shaped
Bourdon tube (A); a helical Bourdon tube (B); flat diaphragm (C); a convoluted
diaphragm (D); a capsule (E); or a set of bellows (F).
|
Sensing Elements
The main types of sensing elements are Bourdon tubes, diaphragms, capsules,and bellows (see Figure 9). The Bourdon tube is a sealed tube that deflects in response to applied pressure. All except diaphragms provide a fairly large displacement that is useful in mechanical gauges and for electrical sensors that require a significant movement.
Mechanical Pressure Gauges.
In mechanical gauges, the motion created by the sensing element is read directly by a dial or pointer. These devices are typically seen in low-performance applications, including blood pressure measurement and automotive pressure gauges. The mechanical approach used to couple the sensing element to the readout can introduce repeatability
Figure 10. Temperature has an effect on the offset of a pressure sensor
|
errors, which will be discussed later. The mechanical mass of the gauges also limits the frequency response and makes these sensors suitable only for slowly changing measurements.
Electromechanical
Sensor Effects. A pressure sensor may be modeled as:
VOUT = kO + k1P | (13) |
where:
kO | = offset |
k1 | = pressure sensitivity in V/pressure unit |
Figure 11. The sensitivity of a pressure sensor is also affected by temperature.
|
Figure 12. The least squares method can be used to measure a pressure
sensor's linearity.
|
Temperature hysteresis refers to the ability of the sensor to give the same output at a given temperature before and after a temperature cycle. Repeatability and hysteresis effects are not easily compensated and are indicators of the basic stability of the device.
Figure 13. Repeatability refers to the ability of a pressure sensor to
provide the same output with successive applications of the same pressure.
|
Gauge factor is a measure of the sensitivity of a sensor. It is defined as the ratio of the change in an electrical transduction parameter over the full range of pressure to the value of that parameter at zero pressure.
Thus, the gauge factor of a resistive sensor is:
R/R | (14) |
where:
R | = base resistance |
R | = resistance change with full-scale pressure, for example |
Potentiometric Pressure Sensors.
Figure 15. Potentiometric pressure sensors use a Bourdon tube, capsule,
or bellows to drive a wiper arm on a resistive element. Such sensors tend
to be inexpensive, but subject to repeatability and hysteresis errors.
|
Inductive Pressure Sensors.
Several configurations based on varying inductance or inductive coupling are used in pressure sensors. They all require AC excitation of the coil(s) and, if a DC output is desired, subsequent demodulation and filtering. The linear variable differential transformer
Figure 16. An LVDT pressure sensor, one configuration of inductive devices,
drives a moving core that varies the inductive coupling between the transformer
primary and secondary.
|
(LVDT) types have a fairly low frequency response due to the necessity of driving the moving core of the differential transformer (see Figure 16).
The LVDT uses the moving core to vary the inductive coupling between the transformer primary and secondary.
Capacitive Pressure Sensors. Capacitive pressure sensors typically use a thin diaphragm as one plate of a capacitor. Applied pressure causes the diaphragm to deflect and the capacitance to change. This change may or may not be linear and is typically on the order of several picofarads out of a total capacitance of 50-100 pF. The change in capacitance may be used to control the frequency of an oscillator or to vary the coupling of an AC signal through a network. The electronics for signal conditioning should be located close to the sensing element to prevent errors due to stray capacitance.
The capacitance of two parallel plates is given by:
C = µA/d | (15) |
where:
µ | = dielectric constant of the material between the plates |
A | = area of the plates |
d | = spacing between the plates |
Figure 17. The basic capacitive pressure sensor consists of two plates with a vacuum between them. |
Since the device has to be fairly large to obtain a usable signal, frequency response may be a problem in some applications. Also, low-pressure capacitive sensors exhibit acceleration and vibration sensitivity due to the necessity for a large, thin diaphragm. A basic capacitive sensor is shown in Figure 17 and a more complex differential pressure capsule is shown in
Figure 18.
Piezoelectric Pressure Sensors. Piezoelectric elements are bi-directional transducers capable of converting stress into an electric potential and vice versa. They consist of metallized quartz or ceramic materials. One important factor to remember is that this is a dynamic effect, providing an output only when the input is changing. This means that these sensors
can be used only for varying pressures.
The piezoelectric element has a
Figure 18. A more complex capacitive pressure sensor can be built to
detect differential pressure.
|
high-impedance output and care must be taken to avoid loading the output by the interface electronics. Some piezoelectric pressure sensors include an internal amplifier to provide an easy electrical interface (see Figure 19).
RO = L/WT | (16) |
where:
= resistivity | |
L, W, T | = length, width, thickness |
|
|
Metallic strain gauges depend only on dimensional changes to produce a change in resistance. A stress applied to the strip causes it to become slightly longer, narrower, and thinner, resulting in a resistance of:
R = (L + L) / (W - W)(T - T), or R RO(1 + 3) | (17) |
As might be expected, the signal due to deformation of the material is small, on the order of 0.1% of the base resistance.
Figure 21. A silicon bar can be bonded to a diaphragm to yield a strain
gauge sensor with a relatively high output.
|
This is called the piezoresistive effect. Following are some of the types of strain gauges used in pressure sensors.
Photo 1. IC processing is used to form the piezoresistors on the surface of a silicon wafer to fabricate an integrated piezoresistive pressure sensor. |
Deposited strain gauge. Metallic strain gauges can be formed on a diaphragm by means of thin film deposition. This construction minimizes the effects of repeatability and hysteresis that bonded strain gauges exhibit.
These sensors exhibit the relatively low output of metallic strain gauges.
Bonded semiconductor strain gauge. A silicon bar may be bonded to a diaphragm to form a sensor with relatively high output. Making the diaphragm from a chemically inert material allows this sensor to interface with a wide variety of media (see Figure 21).
Piezoresistive Integrated Semiconductor.
Piezoresistive Integrated Semiconductor.
IC processing is used to form the piezoresistors on the surface of a silicon wafer (see Photo 1). There are four piezoresistors within the diaphragm area on the sensor. Two are subjected to tangential stress and two to radial stress
when the diaphragm is deflected.
Figure 22. Piezoresistive integrated semiconductor pressure sensors incorporate
four piezoresistors in the diaphragm. When the diaphragm is deflected, two
resistors are subjected to tangential stress and two to radial stress. The
four are connected to a four-element bridge.
|
VOUT/VCC = R / R | (18) |
where:
VCC | = supply voltage |
R | = base resistance of the piezoresistor |
R | = change with applied pressure and is typically ~2.5% of the full R |
Figure 23. The back of a wafer is etched out to form the diaphragm of a piezoresistive pressure sensor. |
The cost of the sensing element is low since a large number of devices fit on a silicon wafer. Typical die size is 0.1 in. square with a 50 mil square
Figure 24. Piezoresistive pressure sensors can be configured to provide
absolute, differential, or gauge pressure readings, depending on the reference.
The diaphragm is shown here as it deflects under applied differential pressures.
|
diaphragm. The circuitry needed for amplification, temperature compensation,and calibration may also be included on the same IC. Various pressure ranges are accommodated by varying the diaphragm thickness and, for very low pressures,
Photo 2. This totally integrated silicon pressure sensor measures 0.52 in. long by 0.44 in. wide by 0.75 in. high, including the port. |
Using a Flow Sensor to Measure Pressure. A recently developed
Photo 3. The recently developed microbridge mass airflow sensor consists of a thin thermally isolated bridge structure suspended over a cavity in the silicon IC. The chip is 67 mil square. |
Because of its small size and excellent thermal resistance, only a few milliwatts of power are required to achieve high air flow sensitivity. By calibrating the device with a flow restriction for a specified pressure drop, a sensor capable of measuring pressures of a few inches of water results.
This is ideal for airflow measurement in HVAC applications, for example.
The sensor operates on the principle of heat transfer due to mass airflow directed across the surface of the sensing element (see Figure 25).
Figure 25. A silicon bar can be bonded to a diaphragm to yield a strain gauge sensor with a relatively high output. |
Photo 4. The output voltage of the microbridge mass air flow sensor varies in proportion to the mass flow of air or other gas through the inlet and outlet ports of the package. The packaged sensor is 1.20 in. wide by 1.24 in. long by 0.61 in. high. |
It consists of a thin film, thermally isolated, bridge structure containing a heater and temperature-sensing elements. The bridge structure provides a sensitive and fast response to the flow of air over the chip. Dual sensing elements flanking a central heating element indicate direction as well as rate of flow. A specially designed housing precisely directs and controls
the airflow across the sensing microstructure. Highly effective thermal isolation for the heater and sensing resistors is attained by the etched cavity air space beneath the flow sensor bridge. The small size and thermal isolation of the microbridge mass airflow sensor are responsible for the remarkably fast response and high sensitivity to flows.
Pressure Switches. Pressure switches, combining a diaphragm or other pressure measuring means with a precision snap switch, can provide precise single-point pressure sensing. Alternatively, simple electronic switches may be combined with electrical sensors to construct a pressure switch with an adjustable set point and hysteresis.
Electrical Interfacing. Care must be taken with the output from a pressure sensor to avoid corrupting the signal by noise or 60 Hz AC pickup.
If the signal must be run some distance to the interface circuitry, twisted and/or shielded wire should be considered. A decoupling capacitor located at the sensor and connected from the supply to ground will also filter noise,as will a capacitor from output to ground.
For long runs, a current output sensor should be considered. These devices have a 2-wire interface and modulate the supply current in response to applied pressure. Obviously, wire resistance has no effect and noise must change the loop current, not simply impress a voltage on the signal.
The industry standard interface is:
PL = 4 mA | (19) |
PH = 20 mA | (20) |
where:
PL | = low pressure range limit |
PH | = high pressure range limit |
Calibration
Figure 26. Dead-weight testers, used to calibrate pressure sensors, incorporate calibrated weights that exert force on a piston which in turn acts on a fluid to produce a test pressure. Oil-type testers like the one shown here are commonly used for high pressures; pneumatic air bearing devices are the usual choice for lower pressures.
|
With this approach, runs of 1000 ft or more are possible.
Manufacturers of pressure sensors have elaborate calibration facilities to verify the accuracy of their production test equipment. These include dead weight testers and temperature-controlled servo-rebalance testers using Bourdon tubes made from high-stability quartz.
A dead-weight tester uses calibrated weights that exert force on a piston which then acts on a fluid to produce a test pressure. For high pressures (>500 psi), oil is typically used (see Figure 26); for lower pressures, pneumatic air bearing testers are available and are much more convenient as well as less messy to use.
Manometer. A mercury manometer is a simple pressure standard and may be used for gauge, differential, and absolute measurements with a suitable reference. It is useful mainly for lower pressure work because the height of the column of mercury will otherwise become unwieldy. The difference in column heights gives the pressure reading (see Figure 27).
Figure 27. The mercury manometer, another calibration option for pressure sensors, can be used on gauge, differential, and absolute sensors with a suitable reference. The difference between column heights gives the pressure reading. Manometers are used mainly to calibrate sensors designed to measure in the lower pressure ranges. |
Many of the higher performance commercially available pressure sensors are furnished with individual test data. A sensor with excellent repeatability and hysteresis makes an excellent low-cost in-house pressure calibration reference when combined with a pneumatic pressure regulator and a source of air pressure (see Figure 28).
Selection of a pressure sensor involves consideration of the medium for compatibility with the materials used in the sensor, the type (gauge, absolute,differential) of measurement, the range, the type of electrical output, and the accuracy required. Manufacturer's specifications usually apply to
Figure 28. A sensor with excellent repeatability and hysteresis can be
combined with a pneumatic pressure regulator and a source of air pressure
to yield an inexpensive in-house pressure calibration reference.
|
Following is a comparison of the two methods.
Given the following error terms:
- Linearity = 1% F.S.
- Null calibration = 1% F.S.
- Sensitivity calibration = 1% F.S. Temperature errors are sometimesgiven as coefficients per ºC referenced to 25ºC. Simply multiplythe coefficient by the temperature range of the application to obtain thetotal error.
- Temperature error = 0.5% F.S.
- Repeatability and hysteresis = 0.1% F.S.
(21) |
Worst case error is equal to the sum of all the maximum errors:
Worst case error = 1 + 1 + 1 + 0.5 + 0.1 = 3.6% | (22) |
Applications
Industrial.
Fluid level in a tank: A gauge pressure sensor located to measure the pressure at the bottom of a tank can be used for a remote indication of fluid level using the relation:
Fluid level in a tank: A gauge pressure sensor located to measure the pressure at the bottom of a tank can be used for a remote indication of fluid level using the relation:
h = P/g | (23) |
Fluid flow: An orifice plate placed in a pipe section creates a pressure drop. This approach is widely used to measure flow because the pressure drop may be kept small in comparison to some other types of flowmeters and because it is impervious to clogging, which may otherwise be a problem when measuring flow of a viscous medium or one containing particulate matter.
The relation is:
(24) |
In some cases, differential pressures of only a few inches of water are measured in the presence of common-mode pressures of thousands of pounds per square inch. These pressure sensors are built with elaborate mechanisms to prevent damage due to the high common-mode pressures and also frequently have remotely controllable pressure ranging.
Automotive.
A wide variety of pressure applications exist in the modern electronically controlled auto.
Among the most important are:
Among the most important are:
Engine oil pressure. Engine lubrication requires pressures of 10-15 psig. The oil pump is sized to achieve this pressure at idle and the pressure increases with engine speed. A potentiometric gauge or pressure switch is used for this function since precision isn't required.
Evaporative purge system leak detection. To reduce emissions,modern fuel systems are not vented to the atmosphere.
This means that fumes resulting from temperature-induced pressure changes in the fuel tank are captured in a carbon canister and later recycled through the engine. Government regulations require that leaks in this system be detected by the on board diagnostics system. One approach is to pressurize the system and measure pressure decay over a fixed time interval. A 1 psig sensor is used for this function.